JA-150ST

Service instructions for JA-150ST

Wireless combined smoke/heat detector

This product is part of the JABLOTRON JA-100 alarm system. It provides indoor fire hazard detection. It is not intended for installation in an industrial environment. It contains an optical smoke detector and a temperature sensor. The optical smoke detector is very sensitive to larger particles, which occur in dense smoke, less sensitive to small particles, which occur in fires of liquids, such as alcohol. Therefore, it also incorporates a temperature sensor, which has a slower response, but is able to detect a fire with a small amount of smoke. The detector responds to the status (it reports activation and also calming of the situation). The product is intended to be installed by a trained technician with a valid Jablotron certificate.

Detector installation
Smoke enters the detector via flowing air - therefore, it must be installed in a place, where the air flows well thanks to natural thermal circulation (usually to the ceiling). The detector can only be used in an enclosed interior. It is not suitable there, where the smoke can spread and cool down (e.g. high ceilings - more than 5 m) - the smoke then does not reach the detector.
In homes, the detector should always be installed in the area leading to the exit (escape route) see Figure 1. If the floor area in the house exceeds 150 m², another detector must be installed there, in another suitable part of the house, see Fig. 2. 

1. kitchen, 
2. living room, 
3. - 6. bedrooms 

? / minimum coverage by detectors

? recommended coverage by detectors



Figure 1



Figure 2



Image 3

It is recommended that a detector be installed in every room where people sleep. 
Installing under horizontal ceilings
If possible, install the detector in the center of the room. Since a cold layer of air may form near the ceiling, the detectors should not be recessed into the ceiling. The fire detector must never be installed in a corner of the room (observe a distance of min. 0.5 m from the room corner, see Figure 4). In corners, air circulates poorly.

Installing under sloping ceilings
If the ceiling does not have a suitable straight surface (e.g. an attic room), the detector can be installed according to Fig. 5.


Fig. 4


Figure 5
The center of the room, the best place, a possible place

Walls, partitions, obstacles, bare-beam ceilings
The detector must be installed at least 0.5 m from a wall or obstruction. If the room is narrower than 1.2 m, the detector must be installed within the middle third of its width. If the room is divided into sections by furniture, shelving or half partitions, above which there is no more than 0.3 m distance from the ceiling, the individual sections should be considered separate rooms. In all directions below and around the detector, a clearance of min. 0.5 m must be left. Any irregularity of the ceiling (such as a support beam), with dimensions greater than 5% of the ceiling height, are considered walls where all the above remains in effect. 

Ventilation and air movement
Detectors shall not be installed directly at the outlet of ventilation, air conditioning and the like. If air is introduced through a perforated ceiling, the ceiling shall not be perforated 0.6 m in all directions around the detector.
Do not install detector:
- There, where air flows poorly (niches, corners, ridges of ceilings at A-roofs and the like).
- There, where it is dusty, smoked or steam occurs
- In places, where the air flows intensively (close to fans, heat sources, mouths of ventilation, draft holes and the like)
- in kitchens and humid areas (steam, smoke and oily vapor can cause false alarms or detection failure)
- next to fluorescent or energy-saving lamps (electrical interference can trigger a false alarm)
- in places with large numbers of small insects 

Caution: Most often the detector becomes unwanted active due to an incorrect installation location.
More detailed installation instructions can be found in TS 54-14 and 34 2710.

Installation
When installing, follow the advice according to the previous paragraphs.




Figure 6: 1 - detach (remove) the detector; 2 - attach (set up) the detector; 3 - optical indication of status; 4 - orientation arrow for setting up; 5 - serial number; 6 - configuration junctions; 7 - place for inserting the batteries 

1. Open the detector screen by turning it to the left (1).
2. Screw on the plastic back panel at the selected location.
3. Adjust the configuration junctions (6) according to the table below
4. Continue to follow the installation manual of the central controller. Basic steps:
a. Select the desired position in the F-Link program on the Peripherals card and start the learning mode with the Add key. 
b. Inserting the last battery into the detector sends the learning code to the system - as confirmation of sending, the signal light (3) flashes briefly.
5. Place the detector on the plastic back panel. It can only be in one position, indicated by arrows (4) on both plastic parts. Turning the detector to the right (2) locks it in place. 

Remark: 
The detector can also learn in the system by entering the serial number (5) through the F-Link program or through the keypad (or bar code reader). All digits below the bar code must be entered (1400-00-0000-0001).

Setting up the detector
In the F-Link program on the peripheral devices card and using the jumpers in the detector, the properties of the detector can be set. 



1 ON Immediate alarm 3 OFF Smoke (EN 54-7) or heat (EN 54-5)
OFF Fire alarm 4 OFF
2 ON memory is on 3 ON only smoke (EN 54-7) (heat not)
OFF memory is off 4 OFF


3 OFF heat only (EN 54-5) (heat not)
4 ON
3 ON Smoke and heat simultaneously (both conditions simultaneously)
4 ON

Forwarding 1 INS selects whether the detector sends the fire alarm or immediate alarm (used when smoke can occur in a normal situation - fireplace, cigarettes, etc.) when it is activated. It applies to the reaction set at the control center Fire or Immediate. If a response other than Basic has been set by the F Link program, the central controller will respond depending on the setting via Response in the peripheral devices map.

Forward link 2 MEM Signaling of alarm memory - if enabled, optical signaling on the detector remains active for 30 minutes after termination of alarm status.
Junctions 3 and 4 SMOKE and TEMP Combination of these junctions determines whether the detector will react to smoke, heat, etc.

Fire alarm
Optical detector: After smoke enters the detector, alarm is activated, the red signal light starts flashing rapidly (approx. 8x per second). The indication remains on until the room is ventilated (and thus the detector's detection chamber).

Temperature sensor: As soon as the temperature exceeds the limit set in the detector, alarm is activated, the red signal light starts flashing rapidly (approx. 8x per second). The indication remains on until the temperature drops e.g. due to ventilation of the room.
Alarm memory: When the alarm memory indication is on, the signal light continues to indicate the activation of the detector by flashing for 30 minutes after the end of the alarm status. The indication can be stopped by activation of the tamper sensor by briefly unscrewing (twisting) the detector.

Sabotage alarm: If the detector is picked up, it sends sabotage signal.

Detector testing and maintenance
Functioning of the detector can be checked by a test spray. The test should be performed once every 30 days. The detector should be regularly cleared of dust, cobwebs and the like, no other maintenance is necessary.

Caution: Never test the detector using the creation of open fire in the object.

Changing batteries in the detector
The system automatically reports when the batteries are running low. A weak battery is also indicated by a flash every 30 sec. Before replacing the batteries in the detector, the system must be switched to Service mode (otherwise sabotage alarms will be called). It is necessary to always replace all three batteries at the same time and use the same type from the same manufacturer. After the batteries are inserted, an autotest automatically starts, checking the voltage of the batteries, the state of the detector and this information is sent to the central controller. 

Fault indication
The detector checks its own operation. As soon as a malfunction is detected, the indicator light continues to flash rapidly for 1 minute and then three short flashes every 30 sec at a time. In this case, take out the batteries for 1 minute and put them back in. If the light starts flashing permanently again after about 1 minute, take the detector to service.

Technical parameters
Power supply 3 pcs alkaline batteries AA 1.5 V, 2.4 Ah)
Typical battery life approx. 2 years
Communication band 868.1 MHz, protocol Jablotron
Communication range approx 300 m (free terrain)
Dimensions diameter 126 mm, height 50 mm
Weight 150 g
smoke detection optical dispersion of light
smoke detector sensitivity m = 0.11 ¸ 0.13 dB/m cf. CSN EN 54-7
temperature detection class A2 cf. CSN EN 54-5
alarm temperature +60°C to +70°C 
operating temperature range -10°C to +80°C
Complies with CSN EN 54-5, CSN EN 54-7, CSN EN 54-25
Further complies with CSN ETSI EN 300220, CSN EN 50130-4, 
CSN EN 55022, CSN EN 60950-1 
Conditions of operation CTÚ VO-R/10/09.2010-11
Meets requirements Regulation No. 23/2008Sb. on fire protection of buildings

1293-CPD-0249

This product is designed and manufactured in accordance with the provisions to be applied to it: Government Decree No. 190/2002 Sb., 426/2000 Sb., in current text, if used according to its intended use. 

Remark: Although this product does not contain harmful materials, do not dispose of it in the domestic waste, but dispose of it at the collection point intended for electronic waste. 
No products

There are no products in this collection. Keep on shopping.

Login

Forgot your password?

Don't have an account yet?
Create account